MCON or MSEP controller display "Motor Power Low"?

Question:
Why does the MCON or MSEP controller display "Motor Power Low" even though the power connections have been checked several times?

Solution:
Each slot must have both axes connected. Or the unconnected axis must be deactivated.

MCON: Parameter 158 - 0: Enabled - 1: Disabled
MSEP: Parameter 33 - 0: Enabled - 1: Disabled

 